    Elevators for Disabled

    Setup and available areas

    Install near entrances connected to accessible pathways for people with disabilities.

    Ensure a clear activity space of 1.4m x 1.4m or larger in front.

    The gap between the elevator floor and the landing floor should be no more than 3 cm.

    Dimensions

    The effective floor area inside the elevator should be at least 1.1m wide and 1.35m deep. For new buildings, ensure a width of at least 1.6m.

    The effective clear width of the entrance door should be at least 0.8m; for new buildings, it should be at least 0.9m.

    User Control Equipment

    The height of the switch should be installed between 0.8m and 1.2m from the floor. However, if there are many switches, this can be relaxed to a maximum height of 1.4m.

    The control panel for wheelchair users inside the elevator should be installed horizontally on the right side, at a height of approximately 0.85m. It should include braille markings for floor numbers for the visually impaired.

    Control panels and communication devices must have braille signs attached.

    Other Equipment

    Install horizontal handrails continuously inside the elevator at a height between 0.8m and 0.9m, or place them on the side and rear with a spacing of no more than 3 cm between handrails.

    If a wheelchair cannot turn 180 degrees in the rear of the elevator, install a sturdy mirror at a height of at least 0.6m on the back wall, allowing the user to check the door status or exit.

    Install a flashing light and audible signal at each landing to indicate the elevator's arrival.

    Inside the elevator, install a flashing light and audible signal to indicate the arrival floor and operational status.

    If a photo-sensing opening/closing device is installed, ensure it can detect objects within a range of 0.3m to 1.4m.

    Install a reopening device.

    Install tactile blocks or use different floor textures within 0.3m in front of the call button.

    Use glass in some parts of the elevator front.

    The button should activate the flashing light and provide audio guidance when pressed.

    If the button is a toggle type, pressing it for the first time should activate the flashing light and provide audio guidance for the selected floor. Pressing it a second time should turn off the light and announce cancellation.

    If the entrances on different floors are not aligned, provide audio guidance for the entrance direction.

    Ensure illumination for the entrance, landing, and controls is at least 150 lux for the safety of users with disabilities.

    Clearly distinguish the call buttons for elevators designated for people with disabilities.

    Attach braille signage for floor numbers to the external call buttons for the accessible elevator.

    Floor Plan and Section MR 60~150m/min

    • Machine Room Floor Plan

    • Machine Room Floor Plan (Parallel)

    • Elevator Shaft Section

    좌우로 페이지를 넘겨서 내용을 확인하세요.
    Passenger Elevator(Code Area: EN-81) [Unit : mm]
    Capacity (Persons) Load Capacity Door Width CAR SIZE 승강로 SIZE PIT Reaction
    Width Depth Height Single Unit Two Units in Parallel
    p KG CENTER OP. W D H W D W D H
    7 550 800 1250 1150 2300 1750 1750 3650 1750 1500
    8 600 800 1250 1250 2300 1750 1850 3650 1850 1500
    9 675 800 1250 1350 2300 1750 1950 3650 1950 1500
    10 750 800 1250 1450 2300 1750 2050 3650 2050 1500
    12 900 900 1600 1350 2300 2100 1950 4350 1950 1500
    13 1000 900, 1000 1600 1400 2300 2100 2000 4350 2000 1600
    15 1150 1000, 1100 1800 1400 2300 2300 2000 4750 2000 1700
    18 1350 1000, 1100 1800 1600 2300 2400 2300 5000 2300 1700
    20 1500 1100, 1200 2000 1600 2300 2600 2300 5400 2300 1800
    21 1600 1100, 1200 2000 1700 2300 2600 2400 5400 2400 1800
    24 1800 1100, 1200 2000 1800 2300 2600 2500 5400 2500 1800
    26 2000 1100, 1200 2100 1900 2300 2700 2600 5600 2600 2000
    30 2300 1100, 1200 2200 2000 2300 2800 2700 5800 2700 2000
    33 2500 1100, 1200 2400 2000 2300 3000 2700 6200 2700 2000
    좌우로 페이지를 넘겨서 내용을 확인하세요.
    Passenger Elevator [Unit : mm]
    Speed Top Floor (O.H)
    M/min min
    60 4500
    90 4700
    105 4750
    120 5100

    Unit: mm. All sizes refer to the interior after architectural finishing. Please account for construction tolerances related to insulation, waterproofing, etc.

    The PIT dimensions are based on a speed of 60 m/min. The PIT depth may vary with increased speed.

    The elevator shaft size, PIT, and overhead (O.H) are recommendations and may be adjusted based on site conditions.

    For Deluxe TYPE applications, add 300 mm to the O.H.

    In principle, there should be no accessible space for people beneath the PIT. Please contact us if this is absolutely necessary.

    If the elevator shaft has glass finishing, laminated glass that complies with KSL 2004 must be used.

    If the elevator shaft has glass finishing, a gallery window or air conditioning should be installed in the overhead machinery space to maintain a temperature below 40 degrees Celsius.

    Communication-related installations such as intercoms and CCTV are excluded from the elevator scope. Please contact us regarding installation locations.

    Floor Plan and Section MRL-W Type 60~105m/min

    • Elevator Shaft Plan

    • Top Floor Elevator Shaft Plan

    • Elevator Shaft Section

    좌우로 페이지를 넘겨서 내용을 확인하세요.
    Passenger Elevator(Code Area: EN-81) [Unit : mm]
    Capacity (Persons) Load Capacity Door Width CAR SIZE Elevator Shaft Size PIT Reaction
    Width Depth Height Single Unit Two Units in Parallel
    p KG CENTER OP. W D H W D W D H
    7 550 800 1250 1150 2300 2250 1950 4650 1950 1700
    8 600 800 1250 1250 2300 2250 1950 4650 1950 1700
    9 675 800 1250 1350 2300 2250 2050 4650 2050 1700
    10 750 800 1250 1450 2300 2250 2150 4650 2150 1700
    12 900 900 1600 1350 2300 2500 2100 5150 2100 1700
    13 1000 900, 1000 1600 1400 2300 2500 2150 5150 2150 1700
    15 1150 1000, 1100 1800 1400 2300 2700 2150 5550 2150 1800
    18 1350 1000, 1100 1800 1600 2300 2900 2400 6000 2400 1900
    20 1500 1100, 1200 2000 1600 2300 3100 2400 6400 2400 2000
    21 1600 1100, 1200 2000 1700 2300 3100 2400 6400 2400 2000
    24 1800 1100, 1200 2000 1800 2300 3100 2500 6400 2500 2100
    26 2000 1100, 1200 2100 1900 2300 3200 2550 6600 2550 2200
    30 2300 1100, 1200 2200 2000 2300 3300 2600 6800 2600 2400
    33 2500 1100, 1200 2400 2000 2300 3500 2600 7200 2600 2400
    좌우로 페이지를 넘겨서 내용을 확인하세요.
    Passenger Elevator [Unit : mm]
    Speed Top Floor (O.H)
    M/min min
    60 5000
    90 5200
    105 5400

    Unit: mm. All sizes refer to the interior after architectural finishing. Please consider construction tolerances for insulation, waterproofing, etc.

    The PIT dimensions are based on a speed of 60 m/min. The PIT depth may vary with increased speed.

    The elevator shaft size, PIT, and overhead (O.H) are recommendations and may be adjusted based on site conditions.

    For Deluxe TYPE applications, add 300 mm to the O.H.

    In principle, there should be no accessible space for people beneath the PIT. Please contact us if this is absolutely necessary.

    If the elevator shaft has glass finishing, laminated glass suitable for KSL 2004 must be used.

    If the elevator shaft has glass finishing, a gallery window or air conditioning should be installed in the overhead machinery space to maintain a temperature below 40 degrees Celsius.

    Communication-related installations such as intercoms and CCTV are excluded from the elevator scope. Please contact us regarding installation locations.

    Floor Plan and Section MOR Type 60~105m/min

    • Elevator Shaft Plan

    • Top Floor Elevator Shaft Plan

    • Elevator Shaft Section

    좌우로 페이지를 넘겨서 내용을 확인하세요.
    Passenger Elevator(Code Area: EN-81) [Unit : mm]
    Capacity (Persons) Load Capacity Door Width CAR SIZE Elevator Shaft Size PIT Reaction
    Width Depth Height Single Unit Two Units in Parallel
    p KG CENTER OP. W D H W D W D H
    7 550 800 1250 1150 2300 2000 1650 4150 1650 1300
    8 600 800 1250 1250 2300 2000 1650 4150 1650 1300
    9 675 800 1250 1350 2300 2000 1750 4150 1750 1300
    10 750 800 1250 1450 2300 2000 1850 4150 1850 1400
    12 900 900 1600 1350 2300 2300 1750 4750 1750 1500
    13 1000 900, 1000 1600 1400 2300 2300 1800 4750 1800 1600
    15 1150 1000, 1100 1800 1400 2300 2500 1800 5150 1800 1700
    17 1275 1000, 1100 1800 1550 2300 2500 1950 5200 1950 1800
    18 1350 1000, 1100 1800 1600 2300 2700 2000 5600 2000 1800
    20 1500 1100, 1200 2000 1600 2300 2900 2000 6000 2000 2000
    21 1600 1100, 1200 2000 1700 2300 2900 2100 6000 2100 2000
    좌우로 페이지를 넘겨서 내용을 확인하세요.
    Passenger Elevator [Unit : mm]
    Speed Top Floor (O.H)
    M/min min
    60 4300
    90 4500
    105 4700

    Unit: mm. All sizes refer to the interior after architectural finishing. Please account for construction tolerances related to insulation, waterproofing, etc.

    The PIT dimensions are based on a speed of 60 m/min. The PIT depth may vary with increased speed.

    For elevators with a capacity of 18 persons or more, add 300 mm to the overhead (O.H).

    The elevator shaft size, PIT, and O.H are recommendations and may be adjusted based on site conditions.

    For Deluxe TYPE applications, add 300 mm to the O.H.

    In principle, there should be no accessible space for people beneath the PIT. Please contact us if this is absolutely necessary.

    If the elevator shaft has glass finishing, laminated glass that complies with KS L 2004 must be used.

    If the elevator shaft has glass finishing, a gallery window or air conditioning should be installed in the overhead machinery space to maintain a temperature below 40 degrees Celsius.

    Communication-related installations such as intercoms and CCTV are excluded from the elevator scope. Please contact us regarding installation locations.

    Electrical Power Requirement

    Exclusion from Scope of Supply and Work